Ingersoll Rand T30 11kw Toschiba 415 volt 21 amps.

by stan
(Kilmore,Vic.Australia.)

Ingersoll Rand T30 compressor with 11kw Toschiba

Ingersoll Rand T30 compressor with 11kw Toschiba

Ingersoll Rand T30 compressor with 11kw Toschiba
Ingersoll Rand T30 compressor with 11kw Toschiba
Ingersoll Rand T30 compressor with 11kw Toschiba

My Ingersoll Rand T30 with a toschiba 11kw 415 volt 21 amp rated compressor will not start with a chinese 6.5kw diesel powered generator.

Photos Attached.
The unit has a master switch panel/control box whereby four wires feed in .The wires are 6.00mm thick.
The wires coming out are 9.00mm thick.
Out of the five wires coming -black is not used and is blanked off.
Therefore red,white,blue and green/yellow are used.
I have grafted the 6.00mm four wires into the master switch box.
These wires are connected correctly alhought of a different guage.
Both the V twin engine and the electrical motors are not seized.
Is there voltage drop or the Chinese generator lacks the OMPH?

Comments for Ingersoll Rand T30 11kw Toschiba 415 volt 21 amps.

Click here to add your own comments

Nov 01, 2013
no start
by: Doug in S.D. CA USA

6.5 kw just ain't gonna handle an 11kw load...

Or is there a typo in your post?