hv02 keeps blowing fuse single phase

by mell
(bridgend uk)

hi my single phase hv02 has been sat in my shed for 3 years while we moved house now dug it out but it keeps blowing the fuse


so took it to local air compressor repair co he told me its the motor rated breakers that need replacing

can someone tell me what are motor rated breakers please

Comments for hv02 keeps blowing fuse single phase

Click here to add your own comments

Aug 25, 2015
Type of breaker
by: Carl

In addition to Dougs answer, again, this is a UK perspective, the normal type of breaker in an electrical system is a B type breaker, for compressors, you need a D type breaker, because it gives a longer delay before it trips.
Carl

Aug 25, 2015
HV02
by: Doug in s.d.ca

Breakers or fuses?

Either way, motor rated have higher / longer trip characteristics to handle large startup power of the type generated by electric motors.

This machine should be drawing about 9.6 A, and I understand normal outlets in the UK are rated 13 A, so you should be OK that way.

I'd suggest you take a look at the section on blows breakers troubleshooting guide here.

Please let us know if I'm wrong about the above as it pertains to the UK and also what you find by the troubleshooter.