COPELAND compressor only runs for 5 sec. at a time

by George Pierce
(Lake Elsinore, Ca.)

The air compressor will only run for 5 sec then shuts off even when first turned on.

It will then wait for several minutes then turn on again for 5 sec.

It repeats this cycle over again until there's too much pressure and the valve blows.

Then it starts over again. thanks for any help you can give. it's a 10 year old COPELAND dental air compressor. thanks alot.... George Pierce






Bill says...

Hmmmm? The valve blows. Am I correct in guessing that it's your PRV valve that blows? At what pressure does that happen?

If it is the PRV that lets go, that and the sequence events that you describe, suggest to me that you need a new pressure switch.

Change the switch out and see. That's a fairly low cost fix if it's the switch that's the problem, or even if it's not.

Cheers,

Bill




Comments for
COPELAND compressor only runs for 5 sec. at a time

Click here to add your own comments

Nov 10, 2010
Compressor start up problem - breaker pops
by: shaikh

whaile compressor start up after 3 minutes breaker tripped with ground fault indication.

_____________________-
Shaikh, you may want to re-post this comment from the Troubleshooting page, under electrical problems so that lots of folks can see it, and perhaps offer more advice for you.

If I understand correctly, your breaker has a GFI element, and the GFI is tripping?

That being the case, it would suggest to me that you have a short, and if it's within the compressor, I would start looking at the pressure switch first.

Good luck.

Bill